THERMOSYPHON RECEIVERS

 

MODEL
AMMONIA
CAPACITY
(kbtu/hr)
R-22 CAPACITY
(kbtu/hr)
DIA LNG A* B* C* D* E F G H
H-TR8X 143 43 8-5/8 49 1-1/4 1-1/2 2 1-1/4 9 32 35 7
H-TR10X 228 68 10-3/4 48 1-1/2 1-1/2 2 1-1/2 9 31 34 8
H-TR12X 405 120 12-3/4 60 2 2 2-1/2 2 10 41 45 9
H-TR14X 575 175 14 72 2-1/2 2-1/2 3 2-1/2 13 50 55 9
H-TR16X 765 230 16 72 3 3 4 3 14 48 53 10
H-TR18X 960 290 18 72 3 3 4 3 14 47 52 11
H-TR20X 1200 360 20 72 4 4 5 4 15 45 51 12
H-TR24X 1900 575 24 78 5 4 5 4 20 44 52 14
H-TR30X 2970 900 30 78 6 5 6 5 21 42 51 15
H-TR36X 4670 1400 36 84 8 6 8 6 23 41 52 20

X = “H” FOR HORIZONTAL OR “V” FOR VERTICAL
* CONNECTIONS A, B, C & D MAY BE ONE SIZE SMALLER FOR R-22
(DIMENSIONS ARE IN INCHES UNLESS NOTED OTHERWISE)

Notes:

  • All prices are FOB our plant, Los Angeles, California.
  • In stock tanks cannot be modified.
  • Standard styles can be modified at nominal cost. The part# will change.
  • DRAWINGS ARE UPDATED TO CURRENT A.S.M.E. DATE FOR NEW ORDERS.
  • If the capacity or working pressure you need is not listed, contact us for a prompt quotation.
  • TANKS SHIPPED BY TRUCK MUST BE SKIDDED FOR SHIPMENT - CALL FOR PRICING.
  • As well as ASME, we can meet other domestic and international codes. EG: ABS, USCG, Canadian, Lloyds and DNV.

SEE CUSTOM REFRIGERATION TANK PAGE FOR OTHER SIZES

Rev. 091920182131